Configuratii standard & Optionale
| eComfort MC 220 - 700 KW | | REFRIGERANT CIRCUIT | R32 | Standard | | R1234ze | | | R513a | | | R134a | | | Winter cooling operation | Optional | | Low leaving water temperature down to -10°C | Optional | | | | SAFETY PACK | Refrigerant leak detection + PRV + acoustic and visual alarms | | | | | COMPRESSOR | Multiscroll | Standard | | Screw | | | Inverter | | | Low noise | Optional | | Super low noise | Optional | | | | EXPANSION VALVE | Thermostatic | | | Electronic | Standard | | | | FAN | AC fan | | | Variable air flow control of condensation : HP floating | Standard | | EC Fan | Standard | | Fan static pressure | | | | | AIR COIL | Standard copper tube/aluminium fin (1) | | | Micro channel heat exchanger (2) | Standard | | Heavy anti-corrosion coil treatment | Optional | | Coils protection guards | Optional | | | | HEAT EXCHANGER | Brazed plate heat exchanger | Standard | | Shell and Tube | | | | | ELECTRICAL | Main disconnect switch | Standard | | Phase reversal protection | Optional | | Antifreeze protection | Optional | | Softstarter | Optional | | Water tank modulating electrical heater (Heat pump) | | | Power factor correction | Optional | | Energy metter | Optional | | | | HYDRAULIC MODULE | Paddle flow switch | Standard | | Electronic flow switch | | | Water filter | Optional | | Flange connection | Optional | | Water tank | Optional | | Low-pressure single pump | Optional | | Low-pressure twin pump | Optional | | High-pressure single pump | Optional | | High-pressure twin pump | Optional | | eDrive high-pressure single pump (variable primary flow) | Optional | | eDrive high-pressure twin pump (variable primary flow) | Optional | | By-pass valve for Delta P control (eDrive) | Optional | | | | CONTROL AND COMMUNICATION | Modbus RS485 communication interface | Optional | | BACnet MSTP communication interface | Optional | | Modbus/BACnet/Ethernet TCP/IP communication interface | Optional | | Basic display | | | Advanced display | Standard | | Service display | Optional | | Remote confort display | Optional | | Extension board for aditional input/output | Optional | | Distance Management System: RedgeCloud connectivuty | Optional | | Distance Management System: RedgeOneWeb | Optional | | | | ENERGY SAVING | Partial heat recovery | Optional | | Total heat recovery | Optional | | Free-cooling | Optional | | | | MISCELLANEOUS | Rubber anti-vibration mounts | Optional | | Spring antivibrations mounts | |
Avantaje
- Instalare si comisionare facile datorita integrarii modulului hidraulic complet cu rezervor.
- Modulare totala a sistemului datorita ventilatoarelor EC si tehnologiei inverter pentru compresoare si pompe.
- Excelente valori SEER si SEPR care depasesc cerintele EcoDesign 2021.
- Control precis al termperaturii apei in modul de incalzire si cel de racire multumita componentelor cu eficienta ridicata.
Sistemul termodinamic
- Compresoare multi-scroll, montate in tandem sau trio, pentru furnizarea celor mai bune eficiente.
- Condensator cu microcanale din aluminiu pentru unitatile doar in racire.
- Ventilatoare de performanta cu palele profilate pentru eficienta ridicata si nivel redus de zgomot (optional).
- Schimbatorul de caldura cu apa este izolat termic si protejat la inghet si este cosntruit din placi din inox, brazat in cupru.
- Unul sau doua circuite independente, fiecare echipat cu valva de expansiune electronica.
- Desuperheater (optional) : schimbator de caldura suplimentar cu placi pe fiecare circuit pentru a recupera caldura rejectata și a furniza apa calda gratuita in scopuri sanitare sau industriale.
Compresor Inverter
- Design optimizat pentru amprenta compacta, inclusiv rezervor de apa (optional).
- Controlul temperaturii apei la iesire este perfect.
- Necesarul rezervorului tampon in cazul unui volum redus de apa sau a unei sarcini termice variabile rapide este redus.
eDrive
Pompa cu viteza variabila, care moduleaza debitul de apa prin schimbatorul de caldura reduce costurile energiei consnumate: - Economiseste consumul de energie in special la sarcina partiala si in perioadele de repaus, ajungand la o reducere de pana la 75% a consumului pompei.
- Economii in sistemul initial, datorita unui numar mai mic de pompe si racorduri decat in cazul sistemelor primar-secundar.
- Flexibilitate si precizie a controlului functionarii pompei: pornire si oprire lina, schimbare graduala a vitezei, precizie si stabilitate a controlului.
- Reducerea solicitarii repetate asupra pompei si conductelor, rezultand o durata de viata mai lunga a echipamentului.
- Eliminarea curentului de pornire datorita acționarii cu frecvența variabila care controleaza alimentarea graduala a motorului pompei.
Control
- Controler electronic eClimatic și parametri de control inteligent care optimizeaza eficienta la sarcina partiala.
- Solutii de comunicatie integrate care ofera flexibilitate (master/slave, Modbus).
- Afișaj DC Advanced, echipat cu un ecran grafic care ofera acces la principalii parametri ai utilizatorului, cu doua afișaje optionale:
- -Afisaj la distanța
- -Afisaj de service
eCLIMATIC
DC Advanced
Carcasa si aspect
- Carcasa din otel galvanizat vopsit in alb.
- Design compact, posibil prin instalarea schimbatoarelor cu dispunere in V.
- Toate componentele termodinamice si hidraulice sunt instalare sub schimbatoare.
Confort acustic
Trei configuratii diferite ale nivelului de zgomot disponibile: - Funcționare silențtoasa (standard), obtinuta prin design compact, compresoare si pompe silentioase si cu ventilatoare cu elice de inalta performanța, toate instalate într-o incinta închisa.
- Optiune de nivel redus de zgomot: izolatia acustica a compresorului de înalta performanta poate prelua zgomotul produs de unitate.
- Sistemul activ de atenuare acustica cu viteza variabilă a ventilatorului permite adaptarea progresiva a unitatii la sarcina cladirii respectand in acelasi timp constrangerile privind nivelul de zgomot si limitele de functionare (optional).
Monitorizare la distanta
- Conectivitate prin RedgeCloud
- BMS prin: e-savvy
e-savvy
Touch panel
Racire- air source
| | | F BOX | | | G BOX | |
|
| Cooling capacity (1) | kW | 213,8 | 250,0 | 292,5 | 326,8 | 362,2 | 405,6 | | Total absorbed power (1) | kW | 67,8 | 79,0 | 97,9 | 105,6 | 118,7 | 135,2 | | EER (1) | 3,2 | 3,2 | 3,0 | 3,1 | 3,1 | 3,0 | | Comfort | Standard Fans | Seasonal Energy Efficiency Ratio (2) | 5.25 | 5.05 | 4.85 | 4.93 | 4.95 | 5.1 | | Application | SEER | | | Seasonal energy efficiency (3) | % | 207 | 199 | 191 | 194 | 195 | 201 | | | s,c | | Process Applica-tion | Seasonal Energy Performance Ratio (4) | | | | | | | | SEPR - High temperature (7°C) | 6.75 | 6.73 | 6.44 | 6.7 | 6.66 | 6.37 | |
| Heating capacity (1) | kW | - | - | - | - | - | - | | Total absorbed power (1) | kW | - | - | - | - | - | - | | COP (1) | - | - | - | - | - | - | | Eurovent energy class (1) - Full load operation | - | - | - | - | - | - | | Comfort | Standard Fans | Seasonal Coeficient of Performance (6) | - | - | - | - | - | - | | SCOP | | Seasonal energy efficiency (7) | % | - | - | - | - | - | - | | s,h | | Seasonal efficiency class (8) | - | - | - | - | - | - | |
| Global sound power level - Standard unit | dB(A) | 90,6 | 92,3 | 92,3 | 92,1 | 92,1 | 94,6 | |
| Maximum power | kW | 93.7 | 108.1 | 128.9 | 143.2 | 158.8 | 180.5 | | Maximum current | A | 155.7 | 175 | 210 | 232.6 | 258.8 | 295.1 | | Starting current | A | 320.4 | 325.6 | 391.8 | 414.5 | 440.8 | 605 | | Short circuit current | kA | 50 | |
| Number of circuits | 2 | 2 | 2 | 2 | 2 | 2 | | Number of compressors | 2+2 | 2+2 | 2+2 | 2+3 | 2+3 | 2+3 | | Total refrigerant load - R32 | kg | 20,2 | 22,4 | 23,8 | 31,0 | 33,5 | 34,0 | |
| Nominal water flow rate | m³/h | 36,9 | 43,1 | 50,5 | 56,4 | 62,5 | 70,0 | | Nominal pressure drop | kPa | 30,0 | 30,4 | 39,3 | 48,6 | 54,8 | 65,9 | |
| Type | Victaulic | | Diameter | 4" |
Racire- air source
| | | H BOX | | | | I BOX | |
|
| Cooling capacity (1) | kW | 437,8 | 478,6 | 531,1 | 573,7 | 615,7 | 659,5 | 694,9 | | Total absorbed power (1) | kW | 138,9 | 155,2 | 171,7 | 181,5 | 197,8 | 214,8 | 231,4 | | EER (1) | 3,2 | 3,1 | 3,1 | 3,2 | 3,1 | 3,1 | 3,0 | | Comfort | Standard Fans | Seasonal Energy Efficiency Ratio (2) | 5.35 | 5.3 | 5.1 | 5.1 | 5.2 | 5.23 | 5.15 | | Application | SEER | | | Seasonal energy efficiency (3) | % | 211 | 209 | 201 | 201 | 205 | 206 | 203 | | | s,c | | Process Applica-tion | Seasonal Energy Performance Ratio (4) | | | | | | | | | SEPR - High temperature (7°C) | 6.9 | 6.66 | 6.61 | 6.7 | 6.67 | 6.64 | 6.47 | |
| Heating capacity (1) | kW | - | - | - | - | - | - | - | | Total absorbed power (1) | kW | - | - | - | - | - | - | - | | COP (1) | - | - | - | - | - | - | - | | Eurovent energy class (1) - Full load operation | - | - | - | - | - | - | - | | Comfort | Standard Fans | Seasonal Coeficient of Performance (6) | - | - | - | - | - | - | - | | SCOP | | Seasonal energy efficiency (7) | % | - | - | - | - | - | - | - | | s,h | | Seasonal efficiency class (8) | - | - | - | - | - | - | - | |
| Global sound power level - Standard unit | dB(A) | 91,8 | 94,5 | 96,2 | 96,1 | 97,6 | 98,0 | 98,4 | |
| Maximum power | kW | 188.7 | 210.4 | 232 | 247.3 | 271 | 288.6 | 306.2 | | Maximum current | A | 307.8 | 344 | 380.3 | 407.1 | 446.5 | 476.6 | 506.7 | | Starting current | A | 489.6 | 653.9 | 690.1 | 716.9 | 756.3 | 786.4 | 816.5 | | Short circuit current | kA | 50 | |
| Number of circuits | 2 | 2 | 2 | 2 | 2 | 2 | 2 | | Number of compressors | 3+3 | 3+3 | 3+3 | 3+3 | 3+3 | 3+3 | 3+3 | | Total refrigerant load - R32 | kg | 43,3 | 48,5 | 49,3 | 55,8 | 60,5 | 61,0 | 61,5 | |
| Nominal water flow rate | m³/h | 75,5 | 82,6 | 91,6 | 99,0 | 106,2 | 113,8 | 119,9 | | Nominal pressure drop | kPa | 38,1 | 45,2 | 46,2 | 53,4 | 61,0 | 60,3 | 66,7 | |
| Type | Victaulic | | Diameter | 5" |
Racire- air source
| | | F BOX | | | G BOX | |
|
| Cooling capacity (1) | kW | 240,1 | 262,4 | 297,2 | 332,5 | | Total absorbed power (1) | kW | 76,1 | 85,7 | 93,2 | 106,3 | | EER (1) | 3,2 | 3,1 | 3,2 | 3,1 | | Comfort | EC Fans | Seasonal Energy Efficiency Ratio (2) | 5.25 | 5.13 | 5.15 | 5.1 | | Application | SEER | | | Seasonal energy efficiency (3) | % | 207 | 202 | 203 | 201 | | | s,c | | Process Appli-cation | Seasonal Energy Performance Ratio (4) | 6.33 | 6.28 | 6.45 | 6.45 | | SEPR - High temperature (7°C) | | Seasonal Energy Performance Ratio (5) | 3.84 | 3.9 | 3.69 | 3.75 | | SEPR - Medium temperature (-8°C) | |
| Heating capacity (1) | kW | | | | | | Total absorbed power (1) | kW | | | | | | COP (1) | | | | | | Comfort | EC Fans | Seasonal Coeficient of Performance (6) | | | | | | Application | SCOP | | | Seasonal energy efficiency (7) | % | | | | | | | s,h | | | Seasonal efficiency class (8) | |
| Global sound power level - Standard unit | dB(A) | 92,9 | 92,9 | 92,7 | 92,7 | |
| Maximum power | kW | 108.5 | 119 | 133.2 | 148.9 | | Maximum current | A | 176.6 | 194 | 216.7 | 243 | | Starting current | A | 418.4 | 435.9 | 458.6 | 484.8 | | Short circuit current | kA | 50,0 | 50,0 | 50,0 | 50,0 | |
| Number of circuits | 2 | 2 | 2 | 2 | | Number of compressors | 2+2 | 2+2 | 2+2 | 2+3 | | Total refrigerant load - R32 | kg | 20 | 22 | 28 | 30 | |
| Nominal water flow rate | m³/h | 41,4 | 45,3 | 51,3 | 57,4 | | Nominal pressure drop | kPa | 28,2 | 31,9 | 40,5 | 46,4 | |
| Type | Victaulic | | Diameter | 4" |
Dimensiuni
Racire - air source
|
| A | | 2772 | 4044 | | B | mm | 2264 | 2264 | | C | | 2421 | 2421 | |
| Basic unit | kg | 1588 | 1690 | 1728 | 2243 | 2263 | 2334 |
Racire - air source
|
| A | | 5326 | 6588 | | B | mm | 2264 | 2264 | | C | | 2421 | 2421 | |
| Basic unit | kg | 2884 | 2915 | 3020 | 3465 | 3531 | 3622 | 3683 |
Racire - air source
|
| A | | 2772 | 4044 | | B | mm | 2264 | 2264 | | C | | 2421 | 2421 | |
| Basic unit | kg | 1618 | 1633 | 2073 | 2092 |
|